Statistical analysis techniques for Partial Discharges measurement under DC voltage

2022

Partial discharges (PD) phenomenon for HVAC (High-Voltage-Alternating-Current) systems has already been widely studied in literature and from this it has been possible to produce a regulatory document that provides indications for description and identification of the different types of discharges. However, the growing diffusion of HVDC (High-Voltage-Direct-Current) systems makes necessary the development of analysis techniques also for DC case. In this paper data obtained from PD measurement under DC voltage were analyzed through the time-frequency map combined with a density-based clustering algorithm. The results show that, with this approach, it's possible to perform a noise rejection a…

Density-Based ClusteringSettore ING-IND/31 - ElettrotecnicaHVDCPartial Discharge (PD)Time-Frequency map2022 IEEE 4th International Conference on Dielectrics (ICD)
researchProduct

Use of Time-Frequency map combined with DBSCAN algorithm for separation of partial discharge pulses under DC voltage

2022

The Phase-Resolved-Partial-Discharge pattern (PRPD) is a conventional technique used for the evaluation of partial discharges (PD) phenomena in High-Voltage-Alternating-Current (HVAC) systems. This map is constructed by plotting the peak of each detected pulses as a function of the phase angle of the supply voltage. Therefore it is obvious that this technique cannot be used for the analysis of data from PD mesaurement under different supply voltage condition (DC). The aim of this paper is to evaluate the application of the Time-Frequency map (TF map) for the analysis of a dataset obtained from PD measurement under DC voltage. A density-based clustering algorithm was also used to gain more i…

Settore ING-IND/31 - ElettrotecnicaTime-Frequency mapPDDensity-Based clustering algorithmPartial Discharge